Supply airflow from sensible load or air changes

Supply airflow in m³/s, m³/h, L/s and cfm, from a room sensible load and supply-to-room temperature difference, or from room volume and air changes per hour.

Method

Sensible-load or ACH airflow with explicit user-selected mode.

It covers two cases: sensible-load method and air-change method. Equations that apply to only one of them are tagged.

Equations

V̇ = Qsρ · cp · ΔTsensible-load method
V̇ = Vr · N3600air-change method

Symbols and units

SymbolQuantityUnit
Inputs
QsRoom sensible loadkW
ρAir densitykg/m³
cpAir specific heatkJ/kg·K
ΔTSupply-to-room temperature differenceK
VrRoom volumem³
NAir changes per hour1/h
Results
V̇Airflowm³/s
V̇Airflowm³/h
V̇AirflowL/s
V̇Airflowcfm

All symbols and units in the library

Assumptions and limits

  • ACH is a user/reference input; no default requirement.

In practice

  • The air-change rate is a project input: take it from the code, authority or client requirement for the space.

Worked example

The input values are the calculator's own verification test, run through the calculator. They show the working; they are not design values.

Method: Sensible-load method.

Inputs

QsRoom sensible load12.06 kW
ρAir density1.2 kg/m³
cpAir specific heat1.005 kJ/kg·K
ΔTSupply-to-room temperature difference10 K

Results

V̇Airflow1 m³/s
V̇Airflow3,600 m³/h
V̇Airflow1,000 L/s
V̇Airflow2,118.88 cfm

A preliminary check for engineer review, not an engineering approval. The project calculation to the applicable codes, authority requirements and specification governs.