Evaporative cooling: leaving air temperature

Air temperature leaving a direct evaporative cooler, and its approach to the wet bulb, from the cooler effectiveness.

Method

Leaving dry-bulb temperature from entering dry-/wet-bulb temperatures and supplied effectiveness.

Equations

t2 = tdb − ε · (tdb − twb)
Δta = t2 − twb

Symbols and units

SymbolQuantityUnit
Inputs
tdbEntering dry bulb°C
twbEntering wet bulb°C
εCooler effectiveness0–1
Results
t2Leaving dry bulb°C
ΔtaApproach to wet bulbK

All symbols and units in the library

Assumptions and limits

  • Water consumption is not calculated.

In practice

  • Take the effectiveness from the cooler manufacturer for the selected media and face velocity.

Worked example

The input values are the calculator's own verification test, run through the calculator. They show the working; they are not design values.

Inputs

tdbEntering dry bulb30 °C
twbEntering wet bulb20 °C
εCooler effectiveness0.5 0–1

Results

t2Leaving dry bulb25 °C
ΔtaApproach to wet bulb5 K

A preliminary check for engineer review, not an engineering approval. The project calculation to the applicable codes, authority requirements and specification governs.

Need the full calculation package?

We prepare project calculations to the applicable codes and your specification, with coordinated drawings.