IYAMAMEngineering Consultancy
HVAC · HVAC-04

U-value and heat transfer through a layered wall or roof

Layer resistances, total thermal resistance, U-value and steady heat flow through a wall, roof or floor made of several layers.

Method

Steady one-dimensional thermal resistance, U-value and Q=UAΔT.

Equations

Rn = dλeach layer
RT = Rsi + Σ(d / λ) + Rso
U = 1RT
Q = U · A · ΔT

Symbols and units

SymbolQuantityUnit
Inputs
AAream²
ΔTInside-outside temperature differenceK
RsiInside surface resistancem²K/W
RsoOutside surface resistancem²K/W
Layers: one row each
dLayer thicknessm
λLayer thermal conductivityW/m·K
Results
RnResistance of each layerm²K/W
RTTotal resistancem²K/W
UU-valueW/m²K
QHeat transferW
QHeat transferkW

All symbols and units in the library

Assumptions and limits

  • Film resistances are supplied, not defaulted.

In practice

  • Enter one row per layer, in any order. Surface resistances are inputs: take them from the standard your project follows.

Worked example

The input values are the calculator's own verification test, run through the calculator. They show the working; they are not design values.

Inputs

AArea10 m²
ΔTInside-outside temperature difference20 K
RsiInside surface resistance0.13 m²K/W
RsoOutside surface resistance0.04 m²K/W

Layers

d (m)λ (W/m·K)
0.10.5

Results

RnResistance of each layer0.2 m²K/W
RTTotal resistance0.37 m²K/W
UU-value2.7027 W/m²K
QHeat transfer540.541 W
QHeat transfer0.540541 kW

A preliminary check for engineer review, not an engineering approval. The project calculation to the applicable codes, authority requirements and specification governs.

Need the full calculation package?

We prepare project calculations to the applicable codes and your specification, with coordinated drawings.