Mixing of two air streams

Dry-air flow, humidity ratio and enthalpy after two air streams mix, for example outdoor air and return air ahead of a coil.

Method

Dry-air mass, water-vapour and enthalpy conservation for steady adiabatic mixing.

Equations

ṁ3 = ṁ1 + ṁ2
W3 = ṁ1 · W1 + ṁ2 · W2ṁ3
h3 = ṁ1 · h1 + ṁ2 · h2ṁ3

Symbols and units

SymbolQuantityUnit
Inputs
ṁ1Stream 1 dry-air mass flowkg/s
W1Stream 1 humidity ratiokg/kg dry air
h1Stream 1 enthalpykJ/kg dry air
ṁ2Stream 2 dry-air mass flowkg/s
W2Stream 2 humidity ratiokg/kg dry air
h2Stream 2 enthalpykJ/kg dry air
Results
ṁ3Mixed dry-air mass flowkg/s
W3Mixed humidity ratiokg/kg dry air
h3Mixed enthalpykJ/kg dry air

All symbols and units in the library

Assumptions and limits

  • Steady state.
  • Adiabatic mixing.
  • No condensation.
  • Common enthalpy reference basis.
  • Dry-air mass basis.

In practice

  • Take W and h of each stream from the psychrometrics note; the flows are dry-air mass flows, not volume flows.

Worked example

The input values are the calculator's own verification test, run through the calculator. They show the working; they are not design values.

Inputs

ṁ1Stream 1 dry-air mass flow1 kg/s
W1Stream 1 humidity ratio0.008 kg/kg dry air
h1Stream 1 enthalpy40 kJ/kg dry air
ṁ2Stream 2 dry-air mass flow3 kg/s
W2Stream 2 humidity ratio0.012 kg/kg dry air
h2Stream 2 enthalpy60 kJ/kg dry air

Results

ṁ3Mixed dry-air mass flow4 kg/s
W3Mixed humidity ratio0.011 kg/kg dry air
h3Mixed enthalpy55 kJ/kg dry air

A preliminary check for engineer review, not an engineering approval. The project calculation to the applicable codes, authority requirements and specification governs.

Need the full calculation package?

We prepare project calculations to the applicable codes and your specification, with coordinated drawings.