IYAMAMEngineering Consultancy
HVAC · HVAC-13

Pump total dynamic head

Pump total dynamic head as the sum of static, pipe friction, fitting, equipment, terminal and other heads along the critical path.

Method

Total dynamic head as the sum of supplied head components; friction is not calculated here.

Equations

H = Hst + Hf + Hfit + Heq + Ht + Ho

Symbols and units

SymbolQuantityUnit
Inputs
HstStatic headm
HfPipe friction headm
HfitFittings headm
HeqEquipment head (coils, heat exchangers, chillers)m
HtTerminal head (control valves, terminals)m
HoOther headm
Results
HTotal dynamic headm

All symbols and units in the library

Assumptions and limits

  • Negative static head is permitted when geometry supports it.

In practice

  • In a closed loop the static lift cancels between supply and return, so the static head is zero; it counts in open systems. Friction is worked out separately and entered here.

Worked example

The input values are the calculator's own verification test, run through the calculator. They show the working; they are not design values.

Inputs

HstStatic head12 m
HfPipe friction head8 m
HfitFittings head3 m
HeqEquipment head (coils, heat exchangers, chillers)5 m
HtTerminal head (control valves, terminals)4 m
HoOther head0 m

Results

HTotal dynamic head32 m

A preliminary check for engineer review, not an engineering approval. The project calculation to the applicable codes, authority requirements and specification governs.