Motor full-load current, input power and torque

Motor full-load current, electrical input, apparent power and shaft torque from the rated output power, voltage, efficiency and power factor.

Method

Motor input, apparent power, full-load current and optional shaft torque.

It covers two cases: three phase and single phase. Equations that apply to only one of them are tagged.

Equations

k = 1single phase
k = √3three phase
Pin = Poutη
S = PinPF
IFL = 1000 · Poutk · U · η · PF
T = 9550 · Poutnwhen the speed is given

Symbols and units

SymbolQuantityUnit
Inputs
PoutRated output (shaft) powerkW
USupply voltageV
ηMotor efficiency0–1
PFPower factor0–1
nSpeed (optional)rpm
Intermediate values
kPhase factor–
Results
IFLFull-load currentA
PinElectrical inputkW
SApparent powerkVA
TShaft torqueN·m

All symbols and units in the library

Assumptions and limits

  • Starting current, breakers, contactors and protection are not estimated.

In practice

  • Use the line-to-line voltage for three-phase motors. The constant 9550 ≈ 60 000 / 2π turns kW and rpm into N·m.
  • Starting current, cable size and protection are separate checks.

Worked example

The input values are the calculator's own verification test, run through the calculator. They show the working; they are not design values.

Method: Three phase.

Inputs

PoutRated output (shaft) power15 kW
USupply voltage400 V
ηMotor efficiency0.9 0–1
PFPower factor0.85 0–1
nSpeed (optional)1,450 rpm

Results

IFLFull-load current28.3015 A
PinElectrical input16.6667 kW
SApparent power19.6078 kVA
TShaft torque98.7931 N·m

A preliminary check for engineer review, not an engineering approval. The project calculation to the applicable codes, authority requirements and specification governs.

Need the full calculation package?

We prepare project calculations to the applicable codes and your specification, with coordinated drawings.