IYAMAMEngineering Consultancy
Plumbing · PHE-09

Hydro-pneumatic tank volume

Nominal volume of a hydro-pneumatic pressure tank from the required drawdown and the tank acceptance factor.

Method

Nominal hydro-pneumatic tank volume from required drawdown and supplied acceptance factor.

Equations

Vt = VdAF

Symbols and units

SymbolQuantityUnit
Inputs
VdRequired drawdownL
AFAcceptance factor0–1
Results
VtRequired nominal tank volumeL

All symbols and units in the library

Assumptions and limits

  • Acceptance factor is a required reference input; it is not derived from pressure settings.

In practice

  • The acceptance factor depends on the pre-charge and the pump cut-in and cut-out pressures; take it from the tank maker’s data.

Worked example

The input values are the calculator's own verification test, run through the calculator. They show the working; they are not design values.

Inputs

VdRequired drawdown100 L
AFAcceptance factor0.5 0–1

Results

VtRequired nominal tank volume200 L

A preliminary check for engineer review, not an engineering approval. The project calculation to the applicable codes, authority requirements and specification governs.